There are four conditions that need to be met when synchronizing a generator or generators to the grid, which are:
- Voltage - Voltage magnitude of the Bus and Line must be the same or within the allowable magnitude set in the synchronizing check relay. Typical settings are at 5% up to 10%.
- Frequency - Frequency must be the same or within the allowable slip frequency between the Bus (Generator) and the Line (Grid).
- Phase Sequence - Phase sequence must be the same sequence i.e. R, Y, B sequence for both Bus and Line.
- Phase Angle - Phase angle for each Bus and Line must be 120 deg apart respectively. The phase angle between e.g. R - Y of Line and R-Y of Bus must be within the maximum allowable angle difference. Typical settings are from 5 deg up to 15 deg. The charge man or competent electrical engineer would normally close the breaker when the synchroscope is close to 000 hrs, which means that the angle difference is closing to 0 deg.